If anti-scalant is being used, be sure to confirm the dose and mix of the solution with the sales rep before starting the system.
This will remove the majority of the air in the system.
The optimal pressure would be 60 PSI.
NOTE: SYSTEM RUNNING PRESSURE CANNOT FALL BELOW 30 PSI
Close the concentrate recycle valve (if applicable) completely by turning it clockwise.
NOTE: The system may need to be shut off and turned back on several times to flush the air out and for the system to continue to run. This may be increased if the sediment filter is not filled with water first.
The pressure should be between 40 - 60 PSI (30 PSI Minimum) during operation to ensure the system will not shut down due to a low pressure fault.
This adjustment is system and site specific. The concentrate valve, concentrate recycle valve, and the throttle valve on the pump will need to be balanced so the RO meets the designed flow rates for each stream without exceeding 150 PSI on the System Pressure Gauge.
CAUTION: Recycle is not always recommended. If the system is on well water, check with our technical support team first to verify water quality is within operat- ing limits permitting recycle.
WARNING: NEVER EXCEED THE MAXIMUM PRESSURE RATING OF YOUR SYSTEM.
Adjust the pump throttle valve and concentrate valve until the correct flow is ach- ieved. For example, DFWHRO-4000 should be adjusted until it produces about 4000 GPD or 2.78 GPM of permeate (product water) at 77°F. The designed flow may be achieved below 150 PSI but it is IMPORTANT not to exceed 150 PSI on the System Pressure when adjusting.