Skip to Content
SUPPORT
Defender SupportRO Start-Up

Defender Support

RO Start-Up

1

Be sure the pre-treatment systems have been flushed and put in service

If anti-scalant is being used, be sure to confirm the dose and mix of the solution with the sales rep before starting the system.

2

If possible, remove the pre-filter and fill it with water

This will remove the majority of the air in the system.

3

Make sure the water supply is turned on and that you have a minimum of 30 PSI to the system

The optimal pressure would be 60 PSI.

NOTE: SYSTEM RUNNING PRESSURE CANNOT FALL BELOW 30 PSI

4

Open the concentrate valve completely by turning it counterclockwise

Close the concentrate recycle valve (if applicable) completely by turning it clockwise.

5

Turn the RO system on

6

Let the system run for 5 - 10 minutes to flush the remaining air out of the filters and membranes

NOTE: The system may need to be shut off and turned back on several times to flush the air out and for the system to continue to run. This may be increased if the sediment filter is not filled with water first.

7

Check the running inlet pressure

The pressure should be between 40 - 60 PSI (30 PSI Minimum) during operation to ensure the system will not shut down due to a low pressure fault.

8

Adjust the system to the designed flow rates without exceeding 150 PSI on the pump / membrane pressure gauge

This adjustment is system and site specific. The concentrate valve, concentrate recycle valve, and the throttle valve on the pump will need to be balanced so the RO meets the designed flow rates for each stream without exceeding 150 PSI on the System Pressure Gauge.

CAUTION: Recycle is not always recommended. If the system is on well water, check with our technical support team first to verify water quality is within operat- ing limits permitting recycle.

WARNING: NEVER EXCEED THE MAXIMUM PRESSURE RATING OF YOUR SYSTEM.

Adjust the pump throttle valve and concentrate valve until the correct flow is ach- ieved. For example, DFWHRO-4000 should be adjusted until it produces about 4000 GPD or 2.78 GPM of permeate (product water) at 77°F. The designed flow may be achieved below 150 PSI but it is IMPORTANT not to exceed 150 PSI on the System Pressure when adjusting.

Need more help?

Ask a different questionDefender Support
Select a different product
Sitemap
ABOUT USAbout UsPrivacy PolicyShipping PolicyRefund & Return Policy